High efficiency furnaces of that brand and production run need to have the condensate collector replaced. The new one will be black poly. There was a recall on the clear units years ago. S1-32816417000 is the JCI part number for the new one.
Recall ended a few years ago (in my area at least), so the part isnt free anymore. They were recalled due to much smaller cracks than that. I like the idea but they used the wrong plastic
And OP if you replace it yourself there will be a colored plastic insert in the inlet (the back) of that exhaust fan. Remove it when the collector box goes on because the new box has that restrictor plate built in. If you run the furnace with two restrictions you’ll get a loud whistling noise
happyrabbitzz
Is that condensation from/in your HVAC? If so, I think it is more than "possible".
RotoGnash
High efficiency furnaces of that brand and production run need to have the condensate collector replaced. The new one will be black poly. There was a recall on the clear units years ago. S1-32816417000 is the JCI part number for the new one.
strikt9
Recall ended a few years ago (in my area at least), so the part isnt free anymore. They were recalled due to much smaller cracks than that. I like the idea but they used the wrong plastic
strikt9
And OP if you replace it yourself there will be a colored plastic insert in the inlet (the back) of that exhaust fan. Remove it when the collector box goes on because the new box has that restrictor plate built in. If you run the furnace with two restrictions you’ll get a loud whistling noise